The Johnson Controls AP-VMA1420-0 variable air Volume Modular Assembly (VMA) is a configurable digital controller, pressure sensor, and/or actuator housed in one pre-assembled unit. Applications include single duct and pressure independent cooling systems.

Features

The Johnson Controls AP-VMA1420-0 integrated module includes a digital controller, pressure sensor, and/or actuator, and is preassembled to reduce installation time. The enhanced actuator ensures a quick response stepper motor that drives the damper from full open to close in 30 seconds or less. Automated Commissioning utilizes Proportional Adaptive (P-Adaptive) and Pattern Recognition Adaptive Control (PRAC) for continuous loop tuning.  Advanced diagnostics offer actuator motor duty cycle, VAV box flow test, damper stall detection, starved box detection, and other diagnostics. Network communications enables integration into a Building Automation System (BAS). Easy configuration provides simple question/answer software format for quick selection of project-specific applications. Software addressing allows remote addressing and identification from a configuration tool.

Applications

Systemssingle duct, dual duct, fan-powered (series or parallel), pressure independent, supply/exhaust
Terminal Box Heatingfloating 3-wire actuator, proportional valve actuator, normally open or closed valve, 1-3 stage electric
Supplemental Heatingfloating 3-wire valve actuator, proportional valve actuator, normally open or closed valve, single-stage electric
Coolingstepper motor damper actuator
Floating/3-wire Incrementalexternal damper and valve
Proportional actuatorExternal damper and valve
Fan-powered terminal boxparallel, temp based, parallel, airflow setpoint, series, on/off control, series, proportional control
LightingOn/Off in relation to occupancy mode
ModesOCC/TEMP OCC/SANDBY/OFF/SHUTDOWN/WINDOW

Product Specifications

Supply Voltage20-30 VAC at 50 or 60 Hz
Optional Fuse Current2.0 amperes
Power Consumption10 VA maximum (Relay and valve requirements not included.)
Ambient Operating Conditions0 to 50°C (32 to 122°F)
Ambient Storage Conditions-40 to 70°C (-40 to 158°F)
Terminations6.3 mm (1/4 in.) spade lugs (Communication has screw terminals.)
Serial InterfacesN2 Bus and Zone Bus. N2 Controller Addressing DIP switch set (1-253) Addresses 254 and 255 are reserved. Software addressable with HVAC PRO software, Release 7.02 or later.
Communications BusN2 between VMA and NCM or N30. Zone Bus between VMA and room sensor (8-pin phone jack or wire to spade lugs or optional plug-on terminals) (Not available when the TE-7720 RF Receiver is applied).
Mounting One screw (included) mounts the VMA1420 to the VAV box. One screw attaches the damper shaft to the actuator, 8 mm (5/16 in.) square head set screw with 44 N-m (389.4 lb-in.) of axial holding power for up to 13 mm (1/2 in.) round damper shafts. Minimum damper shaft length is 44.5 mm (1-3/4 in.).
Housing Plastic housing for controller/actuator with UL94-5VB Plenum Flammability Rating
Dimensions (L x W x H) 153 x 102 x 102 mm (6 x 4 x 4 in.)
Actuator Torque4 N-m (35 lb-in) minimum
Shipping Weight13.1 kg (29 lb) for a box of ten, 1.3 kg (2.8 lb) each
Electrical InputsAnalog Inputs:
Nickel, silicon, platinum (1 K ohm), or NTC (2.25 K) RTD room sensors,
1.6 K setpoint potentiometer (2-wire)
Voltage input for 0-10 VDC (humidity or pressure sensor)
Binary Inputs: Dry contacts
Input configurations vary based on model type.
Velocity PressureVelocity Pressure for 374 Pascal (0-1.5 in. W.C.)
OutputsBinary outputs, 24 VAC triac switched, 25-500 mA loads
Stepper drive, 2 to 767 steps per second (23,000 step resolution)
Analog output, 0-10 VDC @ 10 mA maximum
Standards Compliance CSA 22.2 No. 205, UL 916, UL 864 (UUKL), UL 94-5VB, FCC Part 15, Subpart B, Class A and B, C-tick Australia/NZ, AS/NZS 4251.1, CISPR 22, Class B, CE Directive (89/336/EEC, EN50081-1, EN50082-2) Industrial, IEEE 472, IEEE518, IEEE587 Category A/B, IEC-950, IEC 801-2, -3, -4, -6, -7, -8, ANSI C62.41 A/B